etc-12
|
GE MicroVersaTrip (MVT)
|
| |
|
|
| Lead Time |
Most kits ship in 3 business days. |
Contact GE industrial systems at 1-800-533-5885. |
| Price |
Complete kits for 600A frame breakers cost $1375. |
Contact GE industrial systems at 1-800-533-5885. |
| Versatility |
Programmer is adaptable for all breaker frame sizes. Breaker frame / CT rating can be selected through the menu system without the need for ratings plugs. |
Ratings plugs are required to adapt the Micro Versa Trip to different CT frame sizes and ratings.
|
| Multi-Tapped CT’s are standard. |
Multi-Tapped CT’s available through special order. |
| All programmers come equipped with full LSIG functions which can be defeated if not needed. |
Version with defeatable protection bands is available through special order. |
| Advanced features such as thermal memory for long-time and ground fault, phase imbalance protection are all standard and can be shut off if not needed. |
Thermal memory is used for ground fault but this feature is not defeatable. Phase imbalance is available as an option on the advanced MicroVersa Trip PM. |
Numerous auxiliary devices are available and can be added at any time to a breaker equipped with an etc-12. Most of these accessories are available at low cost and only require the addition of an auxiliary cable and a small control module. Examples of available accessories include:
- Selective Zone interlocks for ground fault and short-time bands.
- MODBUS communications.
- Remote Trip device.
- Latching trip relay.
- Remote flashSAFE activation.
|
Some options available through special order. |
| Display |
Back-light LCD display. |
No backlight. |
| Audible feedback to indicate keystroke. |
No audible keystroke indication. |
| Simultaneous display of all three phases of current plus ground fault current. |
Displays only one phase at a time. |
| Safety |
Standard flashSAFE arc-flash maintenance mode. |
Arc-flash reduction unavailable.
|
| Remote flashSAFE activation module with lockable toggle is available as an option. |
Door mount display available but redundant controls are still located inside the cubicle, this leaves the possibility that the door may be opened on an energized breaker. |
| Standard – remote mountable display that leaves no redundant controls inside breaker cubicle, eliminating any need to open the door on an energized breaker. |
| Setup |
Intuitive setup routine with prompts in plain English. All current values shown in setup are displayed both as a percentage and in actual amps.
|
More complicated setup routine that utilizes numerous symbols and abbreviations. Display shows current values only as a percentage.
|
| “View Settings” menu allows the user to review settings without having to enter the setup menu. |
This feature is unavailable. |
| Trip Logging |
Records and retains trip records for the eight most recent trips.
The current on each phase, plus ground fault (if activated) at time of trip is displayed. |
Only displays most recent trip and shows current only on the phase on which the trip occurred. |
| Testing |
Removable display can be placed near the controls of a primary injection test set, allowing one technician to verify pickups and metering accuracy.
|
A second person is needed to verify display values when primary injection testing.
|
Test Mode which
|
a)
|
Precludes the logging of test trips. |
|
b)
|
Allows test technicians to quickly defeat functions that interfere with their test. |
c)
|
Eliminates the potential for human error by automatically restoring as-found settings. |
|
This feature is unavailable. |
| Communications |
Industry-standard MODBUS capability that can be addressed by any building management system or PLC that is capable of addressing a MODBUS device. Satin Provides a complete list of all MODBUS registers so it can be easily integrated into any compatible system. |
Communications is only available on the advanced MicroVersa Trip PM. The communications system operates on the proprietary GE Power Leader communications bus. |
| Support/Service |
20-year history of providing new generation products that are backwards compatible.
Best in industry, 24/7 support from people who have hands-on breaker experience. |