Available Settings

All trip settings can be entered through the intuitive menu structure which provides prompts in clear and plain English. All pickup oints are displayed both as a percentage, and in actual amps, making the transfer of settings from original trips fast and easy. The below table lists the functions and settings available with every etc-12 retrofit.

FunctionPick Up RangeDelay RangeNotes
Available current sensor tap ratingsN/AN/A40A, 70A, 80A, 100A, 120A, 150A, 200, 225, 300, 400, 600, 800A, 1000A, 1200A, 1600A, 2000A, 2400A, 2500A, 3000A, 3200A, 4000A, 4200A, 5000A, 6000A
Long-time (overload) protectionFrom 25% to 110% of the current sensor tap ratingMIN (5 sec), INT (13 sec), MAX (27 sec) or custom value between 1 and 30 seconds. Delay is reverse I2t and defined by time to trip at 600% of the long-time pickup value.
Short-time protectionFrom 150% to 1000% of the long-time pickup value.Selectable constant or reverse I2t ramp with delays of .070, .100, .150, .200, .300, .400, .500, or .600 seconds.Function can be defeated provided that the Instantaneous protection band is enabled.

Delay can be selected either as a fixed delay or reverse I2t.

Instantaneous protectionFrom 150 to 1200% of the long-time pickup value.Trips breaker in less than .050 seconds.Function can be defeated provided that Short-time protection is enabled.
Ground Fault protectionFrom 10% to 200% of the sensor tap rating, provided that this value does not exceed 1200A. Increments are of 5% of the sensor tap rating up to 100% of tap rating. Above 100% of tap rating, increments are in 10% of tap rating.Selectable constant or reverse I2t ramp with delays of .100, .150, .200, .300, .400 or .500 seconds.Function can be defeated

Delay can be selected either as a fixed delay or reverse I2t.

Phase Imbalance protection.From 15% to 50% ratio of minimum /maximum phase current.Between 1 and 90 secondsFunction can be defeated.
flashSAFE Instantaneous PickupSame as InstantaneousTrips breaker in less than .050 seconds.less than .050 seconds.

May be defeated. Must be lower than the previously entered instantaneous pickup. May be enabled even if instantaneous is defeated.

flashSAFE Ground fault pickup.Same as Ground FaultFixed at .100 seconds w/ no I2t rampMay be defeated. Must be lower than the previously entered ground fault pickup. May be enabled even if ground fault is defeated.
Long-time thermal memoryON or OFFN/A
Ground-fault thermal memoryON or OFFN/A


Communications Configuration
Protocall:MODBUS RTU
Physical Network:RS-485
Baud Rate:9600
Data Bits:8
Stop Bits:2
Parity:None